Power Xpert XGIS compact arc-resistant medium-voltage switchgear

Eaton’s Power Xpert XGIS switchgear is constructed with the majority of the medium-voltage parts fixed-mounted and contained in a laser-welded stainless steel tank suitable for withstanding harsh, corrosive environments. Power Xpert XGIS medium-voltage switchgear delivers an option that is small in size and big in value, with high reliability and enhanced safety to support industrial, oil and gas, data center, utility, mining and infrastructure segments. The enhanced safety, small footprint and virtually maintenance-free design of Eaton’s GIS helps to lower ownership cost and optimize return on investment (ROI).

Voltage
Up to 38 kV
Continuous Current
Up to 2500 A
Interrupt rating
Up to 31.5 kAIC

Core features

  • Front-accessible IP4X rated enclosure
  • No on-site gas filling required
  • Certified to IEC 62271-100, 62271-200
  • Arc resistant classification AFLR (31.5kA for 1 sec)
  • UL Listed

See how the benefits of XGIS makes a big impact

    Take a tour of the Power Xpert XGIS switchgear

    Designed for enhanced safety

    The Power Xpert XGIS gas insulated switchgear’s robust construction and decreased potential for arc faults have been validated through internal arc testing in all medium-voltage areas including cable, breaker, switch and main bus compartments .

    Small footprint

    For many applications, electrical room space is at a premium. The compact design of the Power Xpert XGIS mv switchgear fits into tighter spaces and is suitable for retrofitting into existing locations.

    Virtually maintenance-free

    The breaker, isolating switch and optional ports to connect VTs are contained within a single, SF6-filled, laser welded tank for a high-quality seal with no on-site gas filling required. With an expected lifespan of up to 40 years, the Power Xpert XGIS medium-voltage switchgear offers an impressive long-term value with a low total cost of ownership.

    Eaton’s Electrical Engineering Services and Systems

    With more than 1,500 experts in 60 locations throughout Canada and the U.S., and more around the world, Eaton’s Electrical Engineering Services and Systems team is one of the largest and most experienced service organizations in the industry.
    Specifications

    Ratings

    RATED MAXIMUM VOLTAGE 36/38 kV
    RATED FREQUENCY 50/60 Hz
    CONTINUOUS CURRENT (BREAKER & BUSBAR SYSTEM) 1250 A, 2500 A
    INTERRUPT RATING (BREAKER, BUSBAR SYSTEM, GROUNDING/EARTHING CIRCUIT) Up to 31.5 kA - 3 s rms symmetrical
    RATED PEAK WITHSTAND CURRENT (BUSBAR SYSTEM) 82 kA
    RATED SHORT-CIRCUIT MAKING CURRENT (BREAKER) 82 kA
    BASIC IMPULSE LEVEL (BIL) 36/38 kV - 170kV peak
    POWER FREQUENCY WITHSTAND VOLTAGE 80kV
    INTERNAL ARC CLASSIFICATION AFLR - 31.5 kA - 1s
    ALTITUDE
    Up to 4000 m

    Standards

    IEC 62271 - 1, - 100, - 102, - 200
    THIRD PARTY APPROVAL/RECOGNITION UL, CESI (STL)
    SEISMIC QUALIFICATION IBC and CBC

    Enclosure

    ACCESS
    Front
    INSULATING MEDIUM SF6
    BUS INSULATION Solid Shielded Insulating System
    ENCLOSURE TYPE Indoor, NEMA 1
    EXTERNAL ENCLOSURE DEGREE OF PROTECTION IP2X, IP4X Available
    PRIMARY LIVE PARTS WITHIN AND TANK DEGREE OF PROTECTION IP65
    INDOOR SECTION DIMENSIONS (TYPICAL) 600 mm (23.6") w x 1800 mm (70.9") d x 2700 mm (106.3") h

    Devices

    SWITCHING DEVICE Vacuum circuit breaker
    GROUNDING & ISOLATING DEVICE Three position disconnect switch, open/closed/ready-to-ground
    DEVICE MOUNTING Fixed

    Mechanism

    RATED OPERATING SEQUENCE 0 – 0.3s – CO – 15s – CO A

    Operating conditions
    Normal operating conditions, according to IEC 62271-1 for indoor switchgear.

    Ambient air temperature and humidity
    Less than or equal to 40°C (104°F)
    Less than or equal to 35°C (95°F) on average over 24 hours
    Greater than or equal to -5°C (23°F)
    Relative humidity (for a period over 24 hours) < 95%

    Storage Conditions
    In order to retain all of the functional units qualities when stored for prolonged periods, we recommend that the equipment is stored in its original packaging, in dry conditions sheltered from the sun and rain at a temperature of between -25°C and +55°C