Eaton Arc Quenching Switchgear reduces incident energy to a level where the switchgear will survive an electrical arc flash event, while providing enhanced safety and minimal equipment downtime. Arc Quenching switchgear meets and exceeds the arc-resistant testing requirements of C37.20.7 by demonstrating acceptance even when breakers are removed, doors are open, covers are removed, and without the need for ducts, plenums or special enclosure construction.
Watch the Arc Quenching Switchgear video overview.
Learn more about Arc Quenching Switchgear from our educational video series.
View images of Arc Quenching Magnum DS low-voltage switchgear
VOLTAGE |
Up to 600 V |
CONTINUOUS MAIN BUS CURRENT | 1,600 A to 10,000 A |
SHORT-CIRCUIT TOLERANCE | Up to 100 kA |
CIRCUIT BREAKER AMPS | Up to 6,000 A |
ANSI/IEEE | C37.20.1, C37.51, C37.20.7 |
UL |
1558, 1066, 2748 |
CSA |
C22.2 No 31–10 |
OTHER CERTIFICATION | ABS |
SEISMIC QUALIFICATION | IBC, CBC, UBC Zone 4 |
CONSTRUCTION |
Metal-enclosed |
POWER TERMINATIONS | Rear access, Front access |
INSULATING MEDIUM |
Air |
ENCLOSURE TYPE | NEMA 1 indoor, NEMA 3R outdoor |
INDOOR SECTION DIMENSIONS | 18-60” w x 40-90” d x 96” h |
OVERCURRENT PROTECTION | Power circuit breaker, UL 1066 |
DEVICE MOUNTING | Drawout |