The PDI Static Transfer Switch supplies critical loads with a choice between two available sources of electrical power. By continually monitoring power quality, the PDI Static Transfer Switch automatically transfers to an alternate source within a quarter cycle and without interruption of power to even your most sensitive critical loads.
Ratings | |
Redundancy | Fail safe daul redundant display. Triple redundant logic. Dual redundant gate drivers for SCRs. (Two gate drivers for each SCR) Two output switches available. |
Logic | Power or gate mode (POG). Volt second synchronization Mode (VSS) limits in-rush for 480 volt systems during: -Initial sart up, restarts and transfers. VSS soft start up, restart or transfer limits to 1.5 times in-rush up to 180 degrees out of phase, typically less than 1 time. |
Security | Layered security through log on access. User log-on ID and PIN number required for STS operation. All log-ins are time and date stamped for future reference. Event/alarm memory is 2MB |
Installation and maintenance | - Hot swap capability for printed circuit boards (PCB). - Bypass allows for replacement of PCB while STS is powered and connected to the load. - Hot swap capability for touch screen Graphical User Interface (GUI). - By engaging the rdundant analog control panel, the GUI may be replaced without interrupting power. - Front access onl required for I/R scans of all terminations. - SCR module is on draw-out slides for ease of service. - Logic module is on draw-out slides for ease of service and greater access for I/R scans. |
Monitoring | - Fail safe dual redundant display - Redundant control panel. - All status, event and alarm logs may be viewed via web browser (STS may NOT be operated via the internet). Events will continue to record up to 10 seconds after loss of power. - Real-time capture of wave forms. - Branch circuit monitoring system (BCMS) available. - Graphic depicition of load trends. - Graphic depiction of voltage and current harmonics. - All STS stored data is captured and available at the switch. - Voice assistance for alarms and help. |
Graphical user interface (GUI) | Fully functional touch screen. 10.4-inch LCD touch screen. 640 x 480 resolution. 262K color. Redundant fail safe control panel. |
Communications protocol | Modus TCT/IP Modbus RTU through RS 422/485 port. SNMP. Web enabled through web browser (TCP/IP). Email alerts. NTP time setting. Alarm log download via USB. |